Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01CM05969
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/19/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/18/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* CUSTOMER REQUESTED AFTER HRS. INSP. SEE BELOW FOR RESULTS EIGHTEEN UNITS. 1. CAULK AROUND ALL AC UNITS ON ROOF & MAINT RECEPTS 2. SERVICE LABEL ON UNITS DENOTING CIRCUITRY FED FROM OTHER BLDS. 3. CORRECT PNL SCHEDULES 4. SMOKE DETECTORS TO HAVE NEW BATTERIES |
|
| 01/18/2007 | ELECTRIC - FINAL | Partial Approval | ALL OK -- JUST NEED PLAQUE @ SERVICE -- NEC 230.2E | |
| 01/17/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 13303, 13302, 13203, 13202, 13201, 13301 - ALL OK LABELS FOR SERVICES & LADDER TO INSPECT AC'S NEED TO LOOK AT NORTH 9 UNITS. |
|
| 01/12/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. INSTALL LABEL @ SERVICE -- NEC 230.2E OK UNITS 13103, 13102, 13101 |
|
| 11/28/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. INSTALL FRESH BATTERIES IN SMOKE DETECTORS - NEC 110.3B 2. RANGE ANTI-TIP BRACKETS NOT PROPERLY INSTALLED - NEC 110.3B 3. FINISH EXTERIOR SITE LIGHTING 4. INSTALL BULBS CORRECT WATTAGE IN ALL FIXTURES 5. SHOWER TRIM REQUIRED IN SHOWER LIGHT - NEC 410.4 6. PROVIDE INSTALLATION INSTRCUTIONS FOR SMOKE DETECTORS IT APPEARS SOME MAY NOT BE CORRECTLY LOCATED (SAME MANUFACTURER OF SMOKES) -- 110.3B 7. SMOKE DETECTOR, LIGHTING AND RECEPTACLE WIRING IN BEDROOMS TO COMPLY WITH NEC 210.12B 8. PANEL DIRECTORY NOT CORRECTLY IDENTIFIED - NEC 408.4 9. TIGHTEN ANY LOOSE DEVICES AND REPLACE ANY CRACKED DEVICE COVERS. 10. TIGHTEN WATER HEATER GROUND INSPECTION FOR THE INTERIOR OF UNIT #13103 ONLY CHECK FOR THESE AND OTHER CORRECTIONS THROUGHOUT SERVICE DISCONNECTS DO NOT DISCONNECT ALL UNGROUNDED CONDUCTORS IN STRUCTURE. |