Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - YARD WTR LINE/TEST
Permit Number - T01CM05966
Inspection Description - PLUMBING - YARD WTR LINE/TEST
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/18/2006 | PLUMBING - YARD WTR LINE/TEST | Approved | IVRS - Inspection :* YARDWATER INSTALLED W/O INSPECTION CONTRACTOR POTHOLED PIPING CONNECTIONS LOOK OK |
|
| 12/14/2006 | PLUMBING - YARD WTR LINE/TEST | Not ready for Inspection | IVRS - Inspection :* 1. PROVIDE LETTER FROM ENGINEER ACCEPTING SEWER 2. EXPOSE CONNECTIONS BELOW RBPBP AND AT BLDG. |
|
| 11/30/2006 | PLUMBING - YARD WTR LINE/TEST | Not ready for Inspection | IVRS - Inspection :* 1. YARDWATER PIPING FROM METER TO BLDG. COVERED W/O INSPECTION. 2. EXPOSE METER CONNECTIONS EXPOSE ALL RPPBP CONNECTIONS POTHOLE PIPE FOR VERIFICATION OF DEPTH, MATERIAL TYPE AND SIZE. 3. EXPOSE PIPING BETWEEN MH #5 AND C.O. #11 COVERED WITHOUT INSPECTION PROVIDE TEST RESULTS FOR THIS SECTION. 4. MUST HAVE REVISED APPROVED PLAN WITH DEQ APPROVAL AND ALL TEST RESULTS FOR ALL PIPING AND MANHOLES. |