Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01CM05961
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/17/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/13/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED APPROVED EXTENDER RING 314.20 2. USE APPROVED HARDWARE FOR DEVICES - NOT DRYWALL BOXES. |
|
| 09/10/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 14106 1. SMOKE DETECTORS TO BE MINIMUM 36" FROM HVAC VENTS 2. ALL 120V OUTLETS (LIGHTS, SMOKES, RECEPTACLES) REQUIRE ARC FAULT PROTECTION IN BEDROOMS 3. PANEL DIRECTORY NOT CORRECTLY IDENTIFIED 4. INSTALL RANGE INSPECTION FOR THIS UNIT ONLY - GO THROUGH ALL UNITS BEFORE CALLING IN 5. RANGES REQUIRED FOR FINAL |