Permit: T01CM05961

Parcel: 10824013F


Addresses:

2550 E RIVER RD 14


Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Permit Number - T01CM05961

Inspection Description - ELECTRIC - CABLE DROP

Inspection Status - Approved

Date Description Inspector Results Comments
12/18/2006 ELECTRIC - CABLE DROP Approved IVRS - Inspection :*
12/06/2006 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
The service is not per code.| 210*
1. INSTALL PROPER SIZE BONDING CONDUCTORS FOR SERVICE RACEWAYS -- NEC 250.102(C)
2. INSTALL ADDRESS ON SERVICE
3. IDENTIFY ALL SERVICE DISCONNECTS AND UNIT NUMBERS
NEC 230.70(B)
4. GO THROUGH AND RE-TORQUE ALL SCREWS -- NEC 110.3
5. PROVIDE PLAQUE CONCERNING BRANCH CKTS OTHER THAN THOSE SUPPLIED BY SERVICE DISCONNECTS, IE FIRE BELL, LIGHTING, ETC.
6. CHECK UFER
09/26/2006 ELECTRIC - CABLE DROP Not ready for Inspection IVRS - Inspection :*