Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01CM05957
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/02/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/30/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELLED |
|
| 01/29/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. DIFFERENT SIZE GROUNDS UNDER SAME TERMINATION IN PANELS 2. IDENTIFY WHITE USED AS HOT 3. SMOKE DETECTORS MISSING IN GARAGES 4. GARAGE GFI SHOWS OPEN NEUTRAL 5. OPEN WIRING ON EXTERIOR & LIGHTING J-BOX NOT MADE UP 6. IRRIGATION PANEL LOOSE FROM WALL/NOT TO BE IN FRONT OF PANEL 7. HAVE LOOSE DEVICES, DEAD CKT IN STAIRWELL 8. HALF HOT NOT WORKING 9. INSTALL ALL PLATE SCREWS 10. ANTI-TIP DEVICE ON RANGE |
|
| 01/26/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELLED |