Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01CM05956
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/17/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* PNL TERMINATIONS LOOSE DRYER - OK REINSTALL KIT BULBS OK WEATHERPROOF CAULKING AROUND AC DISCONNECTS IDENTIFICATION AT SERVICE |
|
| 11/16/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 10/31/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* PROVIDE PLANS - CHECK FOR THESE CORRECTIONS IN ALL STRUCTURE. 1. PROVIDE GFI PROTECTION FOR GARAGE RECEPTACLE FOR ALARM TRANSFORMER OR SINGLE RECEPTACLE - NEC 200.8 2. BOND WIRE NOT TO BE UNDER SAME TERMINATION IN SUB-PANELS -- NEC 110.14 3. PANEL DIRECTORY NOT CORRECTLY IDENTIFIED -- NEC 408.4 4. NEED WALL SWITCHED LIGHT OR RECEPTACLE IN SLEEPING AREA -- NEC 210.70 5. HAVE SEVERAL LOOSE RECEPTACLES THROUGHOUT - NEC 406.4 A, B 6. ALL WIRING PROVIDING 15 AND 20 AMP OUTLETS INTO BEDROOM NEEDS ARC FAULT PROTECTION - NEC 210.12 B 7. NEED CONNECTOR FOR DISHWASHER CORDS - NEC 400.14 8. NEED COVER FOR RANGE RECEPTACLE AND MAKE SURE BONDING STRAP IS REMOVED FROM RANGE J-BOX 9. INSTALL ALL SCREWS IN SERVICE/FINISH EXTERIOR LIGHTING. |
|
| 10/27/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |