Permit: T01CM05956

Parcel: 10824013F


Addresses:

2550 E RIVER RD 17


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T01CM05956

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/17/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
PNL TERMINATIONS LOOSE DRYER - OK
REINSTALL KIT BULBS OK
WEATHERPROOF CAULKING AROUND AC DISCONNECTS
IDENTIFICATION AT SERVICE
11/16/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
10/31/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
PROVIDE PLANS - CHECK FOR THESE CORRECTIONS IN ALL STRUCTURE.

1. PROVIDE GFI PROTECTION FOR GARAGE RECEPTACLE FOR ALARM TRANSFORMER OR SINGLE RECEPTACLE - NEC 200.8
2. BOND WIRE NOT TO BE UNDER SAME TERMINATION IN SUB-PANELS -- NEC 110.14
3. PANEL DIRECTORY NOT CORRECTLY IDENTIFIED -- NEC 408.4
4. NEED WALL SWITCHED LIGHT OR RECEPTACLE IN SLEEPING AREA -- NEC 210.70
5. HAVE SEVERAL LOOSE RECEPTACLES THROUGHOUT -
NEC 406.4 A, B
6. ALL WIRING PROVIDING 15 AND 20 AMP OUTLETS INTO BEDROOM NEEDS ARC FAULT PROTECTION - NEC 210.12 B
7. NEED CONNECTOR FOR DISHWASHER CORDS - NEC 400.14
8. NEED COVER FOR RANGE RECEPTACLE AND MAKE SURE BONDING STRAP IS REMOVED FROM RANGE J-BOX
9. INSTALL ALL SCREWS IN SERVICE/FINISH EXTERIOR LIGHTING.
10/27/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*