Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/02/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/30/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELLED |
|
| 01/29/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. HOUSE PANEL DIRECTORY NOT PROPERLY IDENTIFIED NEC 408.4 2. PANEL DIRECTORY WEST UNIT NOT PROPERLY IDENTIFIED NEC 408.4 3. DIFFERENT SIZE EQUIPMENT GROUND NOT ALLOWED UNDER SAME TERMINATIONS IN SUB-PANELS NEC 110.3 B 4. STRAP FLEX TO AC UNIT - NEC 350.30 5. IDENTIFY WHITE USED AS HOT - NEC 200, 310 |
|
| 01/25/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |