Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/04/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 03/01/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*NOTES OK TEMP C OF O. NO MECHANCIAL WORK DONE OR PERMITTED PER PLANS. HOWEVER UPON ROOF INSPECTION NOTICED BURNED HOLE IN J-BOX FOR AC UNIT CAUSED BY BAD SPLICE, PLEASE HAVE ELECTRICAL CONTRACTOR REPAIR, AS THIS MAY CAUSE FIRE HAZARD, SWITCH IS OFF. |
| 02/26/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*1.) EMERGENCY & EXIT LIGHTING NOT IDENTIFIED IN LOAD CENTER NOT TESTABLE. 2. )PANEL MISSING CIRCUIT DIRECTORY. 3.) DISCONNECT SWITCH FOR 400 H2 NOT IDENTIFIED. 4.) 400 HW RECEPTACLES NOT IDENTIFIED 5.) NEED ACCESS TO ROOF FOR INSPECTION OF A/C EQUIPMENT DISCONNECTS IDENTIFICATION, FUSING ETC. CORRECT ALL OF THE ABOVE & RECALL HAVE LADDER TO ROOF ON NEXT INSPECTION. |
| 02/11/2002 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |