Permit: T01CM05896

Parcel: 12416023A


Addresses:

1036 S EUCLID AV


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T01CM05896

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
02/14/2002 PLUMBING - INTERMEDIATE Approved IVRS - Inspection 0000*1.) ALL CORRECTIONS MADE OK 2.) ABS DWV OK WATER TEST OK 3.) COPPER OK PRESSURE TEST OK 4.) OK TO COVER WALLS.
02/13/2002 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*1.) REVIEW 712.2 WATER TEST 94UPC ALL PIEP AND EVERY FITTING IN THE BLDG NEEDS TO BE TESTED (OR PORTION IN YOUR SCOPE OF WORK.)
02/11/2002 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*1.) THERE IS NO UNDERSLAB ON THIS CONTRACT, ALL WORKS IS ABOVE GRADE 2.) THE POINT OF VENT MAY NOT BE BELOW THE WEIR OF THE TRAP 3.) A TRAP MUST BE THE SAME SIZE AS THE TRAP ARM TO WHICH IT IS CONNECTED. 4.) A N/H" BAND IS NOT APPROVED FOR ABS. 5.) NO WATER TEST ON ABS 6.) HAVE PLUMBER CHECK ALL WORK.