Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T01CM05896
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/14/2002 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection 0000*1.) ALL CORRECTIONS MADE OK 2.) ABS DWV OK WATER TEST OK 3.) COPPER OK PRESSURE TEST OK 4.) OK TO COVER WALLS. | |
02/13/2002 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999*1.) REVIEW 712.2 WATER TEST 94UPC ALL PIEP AND EVERY FITTING IN THE BLDG NEEDS TO BE TESTED (OR PORTION IN YOUR SCOPE OF WORK.) | |
02/11/2002 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999*1.) THERE IS NO UNDERSLAB ON THIS CONTRACT, ALL WORKS IS ABOVE GRADE 2.) THE POINT OF VENT MAY NOT BE BELOW THE WEIR OF THE TRAP 3.) A TRAP MUST BE THE SAME SIZE AS THE TRAP ARM TO WHICH IT IS CONNECTED. 4.) A N/H" BAND IS NOT APPROVED FOR ABS. 5.) NO WATER TEST ON ABS 6.) HAVE PLUMBER CHECK ALL WORK. |