Permit: T01CM05896

Parcel: 12416023A


Addresses:

1036 S EUCLID AV


Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T01CM05896

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
02/13/2002 FRAMING Approved IVRS - Inspection 0000*
02/11/2002 FRAMING Partial Approval IVRS - Inspection 0000*1.) I AM AWARE OF BUILDING CODE REQUIREMENTS BUT WHEN AS-BUILT DEVIATES FROM APPROVED PLANS THE CITY OF TUCSON REQUIRES APPROVED REVISIONS. 2.) OK TO COVER FRAME WITH GYP BOARD BUT YOU MUST HAVE AS-BUILT PLAN SUBMITTED TO DEVELOPMENT SERVICES. 3.) INCLUDE ANY REVISION THAT USES MASONRY FOR IN-FILL OF DOORWAY.
02/07/2002 FRAMING Denied IVRS - Inspection 0999*1.) PLAN CALLS FOR 3X6 LEDGER NOT 2 X6 2.) 1/2" ANCHOR BOLTS @32" O.C. NOT INSTALLED IN LEDGER 3.) DOUBLE TOP PLATE OF WALLS CALLED FOR ON PLAY.4.) POWER DRIVEN STUDS IN SOLE PLATE MISSING. 5.) PLAN CALLS FOR IN-FILL OF EXISTING WALL TO BE WOOD FRAME FIRE WALL. YOU HAVE INSTALLED MASONRY. 6.) G.S.N. #7 CALLS FOR GRADE #1 LEDGERS YOU HAVE USED GRADE #2 FOR OFFICE AREA. 7.) REVISE PLANS TO REFLECT AS-BUILT.
02/01/2002 FRAMING Not ready for Inspection IVRS - Inspection 0000*