Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T01CM05896
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/13/2002 | FRAMING | Approved | IVRS - Inspection 0000* | |
02/11/2002 | FRAMING | Partial Approval | IVRS - Inspection 0000*1.) I AM AWARE OF BUILDING CODE REQUIREMENTS BUT WHEN AS-BUILT DEVIATES FROM APPROVED PLANS THE CITY OF TUCSON REQUIRES APPROVED REVISIONS. 2.) OK TO COVER FRAME WITH GYP BOARD BUT YOU MUST HAVE AS-BUILT PLAN SUBMITTED TO DEVELOPMENT SERVICES. 3.) INCLUDE ANY REVISION THAT USES MASONRY FOR IN-FILL OF DOORWAY. | |
02/07/2002 | FRAMING | Denied | IVRS - Inspection 0999*1.) PLAN CALLS FOR 3X6 LEDGER NOT 2 X6 2.) 1/2" ANCHOR BOLTS @32" O.C. NOT INSTALLED IN LEDGER 3.) DOUBLE TOP PLATE OF WALLS CALLED FOR ON PLAY.4.) POWER DRIVEN STUDS IN SOLE PLATE MISSING. 5.) PLAN CALLS FOR IN-FILL OF EXISTING WALL TO BE WOOD FRAME FIRE WALL. YOU HAVE INSTALLED MASONRY. 6.) G.S.N. #7 CALLS FOR GRADE #1 LEDGERS YOU HAVE USED GRADE #2 FOR OFFICE AREA. 7.) REVISE PLANS TO REFLECT AS-BUILT. | |
02/01/2002 | FRAMING | Not ready for Inspection | IVRS - Inspection 0000* |