10/10/2002 BUILDING - FINAL Approved IVRS - Inspection 0000*/ 1) APPROVAL FOR FINALS ONLY
06/12/2002 BUILDING - FINAL Partial Approval IVRS - Inspection 0000*/ 1) FOR FINALS ONLY, BUILT WITHOUT PERMIT OR INSPECTIONS 2) #6 WIRE IN SEVICE PANEL REQUIRES A 60 AMP BREAKER 2) COLOR CODE GREEN WIRE TO A NEUTRAL IN SERVICE 3) LOCATE ONE GROUND ROD AT OUT BLDG AND GROUND ELECTRODE CONDUCTOR IN SUB-PANEL 4) 60 AMP SQUARE D BREAKER PROTECTING A #10 CU CIRCUIT, 30 AMP REQUIRED 5) USE SCH. 80 NON METALLIC CONDUIT EXPOSED AT WALLS 6) PLAN PANEL SCHEDULE IS WRONG CALLS FOR 20 AMP BREAKERS ON 14 GAUGE WIRE ( SHOULD BE #14+15 AMP BREAKER 7) 30 AMP SUB-PANEL FEED DOUBLE LUGGED AT 100 AMP MAIN