Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date |
Description |
Inspector |
Results |
Comments |
| 03/25/2002 |
ELECTRIC - CABLE DROP |
|
Approved |
IVRS - Inspection 0000* |
| 03/07/2002 |
ELECTRIC - CABLE DROP |
|
Denied |
IVRS - Inspection 0215* SEE NOTES FROM NEW METER/MAIN/LOADCENTER. 1.) THE NEW METER/MAIN LOAD CENTER MUST BE GROUNDED FROM THE NEUTRAL TO THE COLD WATER AND GAS LINES. 2.) EXISTING PANEL "A" WILL BECOME A "SUB PANEL" AND IT WILL BE NECESSARY FOR YOU TO ISOLATE THE NEUTRALS AND GROUNDS. 3.) THE CABLE TO FEED PANEL "A" WILL HAVE TO BE OF A SIZE LARGE ENOUGH TO CONDUCT THE 125 AMP REMAIN BREAKER RATING. THE CABLE WILL HAVE TO CONTAIN 2 HOTS, 1 NEUTRAL, AND A GROUND |
| 03/06/2002 |
ELECTRIC - CABLE DROP |
|
Denied |
NO ANSWER TO DOOR NO ONE HOME 10AM PLEASE RECALL & LEAVE MESSAGE. |
| 03/01/2002 |
ELECTRIC - CABLE DROP |
|
Denied |
IVRS - Inspection 0215*1.) WHERE ARE THE A WATER BOND & B. THE GAS LINE BOND TO GROUNDING SYSTEM? |