Permit: T01CM05891

Parcel: 128140620


Addresses:

5238 E 18TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
03/26/2002 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
02/07/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*PENDING INSTALLATION OF NEW SVC. GEAR.
02/05/2002 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0245*1.) LEAVE GROUND PIGTAILS AT SWITCH BOXES. ALL SWITCHES ARE REQUIRES TO BE GROUNDED. 2.) EXIT LIGHT (CIELING MTD.) OVER SIDE DOOR, OUTLET IS MISSING. 3.) LIGHTING REARRANGED I BATHROOM IN HALL. MARK RED LINE CHANGES ON PLAN. NOTE ALL RECEPTACLES ADDED. CLOSETS IN BEDROOMS NOT SHOWN ON PLAN. 4.) SIDE DOOR EXTERIOR LIGHTING NOT PER PLAN. 5.) INSTALL 1/2" FLEX CONDUIT SLEEVE FOR 102 G. ROME TO WTR. HTR. FIRMLY J HOOK STRAP TO 2 X 4 SO IT WILL NOT FALL OFF. 6.) USE"FAN RATED CIELING BOXES IN BEDROOMS. CORRECT & RECALL.