Inspection History: REINFORCED MASONRY PRE-GROUT

Date Description Inspector Results Comments
01/09/2002 REINFORCED MASONRY PRE-GROUT Approved IVRS - Inspection 0000*
01/08/2002 REINFORCED MASONRY PRE-GROUT Denied IVRS - Inspection 0999*/ 1) CELLS TO DIRTY TO POUR GROUT
01/07/2002 REINFORCED MASONRY PRE-GROUT Denied IVRS - Inspection 0999*/ 1) BLOCK CELLS FOR VERTICAL REBAR TOO DIRTY (BLOCKED WITH GROUT) CLEAN OUT AND INSTALL VERTICAL REBAR 2) BOND BEAM REQUIRES 2 EACH #4 REBAR ONLY ONE INSTALLED-REBUILD
12/31/2001 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000*/ 1) 4' LIFT OK