Permit: T01CM05823

Parcel: 13707037A


Addresses:

330 W NEBRASKA ST


Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Permit Number - T01CM05823

Inspection Description - ELECTRIC - CABLE DROP

Inspection Status - Approved

Date Description Inspector Results Comments
11/22/2002 ELECTRIC - CABLE DROP Approved
08/27/2002 ELECTRIC - CABLE DROP Not ready for Inspection IVRS - Inspection 0000*MUST HAVE A PERFORMANCE TEST OF 1200 AMP BREAKER GFCI PRIOR TO CLEARANCE PLEASE ADJUST DOOR TO LATCH IN PLACE W/AT LEAST A 90 OPENING. NEED COMPANY LETTERHEAD THAT SWITCHGEAR AND SUBPANEL HAVE BEN TORQUED TO MAN. SPECS FASTEN SWITGEAR AND NEED GROUNDING ELECTRODE FOR TR. POST BOND COMPLETE PANELS AND SIGN OF SHEET. CERTAIN COMPLETION WILL BE REQUIRED.