Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
Permit Number - T01CM05823
Inspection Description - ELECTRIC - CABLE DROP
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/22/2002 | ELECTRIC - CABLE DROP | Approved | ||
| 08/27/2002 | ELECTRIC - CABLE DROP | Not ready for Inspection | IVRS - Inspection 0000*MUST HAVE A PERFORMANCE TEST OF 1200 AMP BREAKER GFCI PRIOR TO CLEARANCE PLEASE ADJUST DOOR TO LATCH IN PLACE W/AT LEAST A 90 OPENING. NEED COMPANY LETTERHEAD THAT SWITCHGEAR AND SUBPANEL HAVE BEN TORQUED TO MAN. SPECS FASTEN SWITGEAR AND NEED GROUNDING ELECTRODE FOR TR. POST BOND COMPLETE PANELS AND SIGN OF SHEET. CERTAIN COMPLETION WILL BE REQUIRED. |