Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T01CM05822

Parcel: 10707016F


Addresses:

1306 W GRANT RD


Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Permit Number - T01CM05822

Inspection Description - ELECTRIC - CABLE DROP

Inspection Status - Approved

Date Description Inspector Results Comments
09/04/2002 ELECTRIC - CABLE DROP Approved IVRS - Inspection 0000*
06/24/2002 ELECTRIC - CABLE DROP Partial Approval IVRS - Inspection 0000*OK 3/4" PVC FROM SIGN TO SERVICE 2.) PLEASE PROVIDE A LETTER ON COMPANY LETTER HEAD VERIFYING TORQUE VALVES AS STATED IN ADAPTER KIT INSTRUCTIONS 2.) RECALL AFTER CROSS OVER. OK TO CLEAR UPGRADE OK CABLE DROP CALLED
06/18/2002 ELECTRIC - CABLE DROP Denied IVRS - Inspection 0999*1.) BONDING DEVICES ARE NEED ON BOTH SIDES OF SERVICE NIPPLES 250-94. 2.) A SEALING DEVICE IS NEED FOR ENTRANCE ABOVE BUSSING 3.) THE GROUNDING ELECTRODE CONDUCTOR TO BE CONNECTED TO GROUNDED CONDUCTOR 250-24. 4.) PLEASE MAINTAIN WORKING CLEARENCES AT SERVICE 110-26. 5.) DISCONNECT CALLED FOR 2 POLE WITH CLASS "T" FUSES. WE HAVE 3 POLES WITH CLASS "R" FUSES OR CLASS "J" FUSES.
05/30/2002 ELECTRIC - CABLE DROP Partial Approval IVRS - Inspection 0000*1.) PLEASE INSTALL ALL STRANDS OF SHIELD WIRE UNDER TERMANAL LUG. 2.) CONDUIT TO BE SUPPORTED AS PER CODE. 3.) TIGHTEN FITTINGS TO SMART CONTROLLER. 4.) FILL UNUSED OPENINGS IN GUTTER. 5.) NEW PANEL SCHEDULE DOES NOT REFLECT TWIN BREAKERS BEING USED PLEASE VERIFY PLEASE VERIFY ALSO WHAT LOADS ARE TAPED OFF BOTTOM UP BUSS? 6.) TIGHTEN CONDUCTOR TREMANATIONS 7.) WE HAVE MULTI POLE CONDUCTORS UNDER LOGS AT PANEL BUSS. 8.) THERE IS NO GROUND BAR INSTALLED AT PANEL A PLEASE SEPERATE GROUND AND NEUTRAL. 9.) WHAT ARE CONDUCTORS FOR IN JUNCTION BOX BX POOR AND INSTALL COVER. 10.) CLEAN SURFACE UNDERGROUND BAR. 11. LOW VOLTAGE AND REGULAR VOLTAGE NEED TO BE SEPERATED IN GUTTER. 12.) FINISH SEAL OFF FOR CANOPY LIGHTS.