Inspection History Details
Inspection Status: Partial Approval
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T01CM05802
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/18/2002 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*1ST FLOOR ONLY SEC SEC 603.2.3. BACK FLOW DEVICE ACCESS. | |
04/10/2002 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999*1.) 4" HORIZONTAL DRAIN MUST HAVE HANGERS LOCATED WITHIN 18" MAX FROM COUPLINGS 2.) SOIL WATER TEST IS OK ON 4". 3.) CAN NOT HAVE 2" TRAP ARMS ON LAVATORS AND DRINKING FOUNTAIN. TRAP SIZE CAN ONLY BE 1 PIPE SIZE LARGER THAN OUTLET OF FIXTURE RE-TEST SYSTEM. 4.) TRAP PRIMER CONNECTION @ P-TRAP REQUIRES BRASS NIPPLE. |