Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 02/04/2002 |
ELECTRIC - ABOVE CEILING |
|
Approved |
|
| 01/31/2002 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*1.) PLEASE DO NOT WRAP ELECTRIC WHIP FROM FIXTURES AROUND SPINKLER PIPE 2.) FIXTURE NEED TO BE ATTACHED WITH WIRES ON OPPISITE SIDES. |
| 01/22/2002 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*1.) ITEM 2-8 OF PREVIOUS INSPECTION COMPLETED OK FOR TEMP C OF O SUBJECT TO OTHER INSPECTIONS. |
| 01/20/2002 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*1.) MISSING FIXTURES DUE TO BACK ORDERING. TEMP LIGHTS ARE INSTALLED 2.) NEED DISCONNECTING MEANS FOR WATER HEATER 3.) LABEL PANEL ON OUTSIDE COVER AND NEED A CIRCUIT DIRECTORY. 4.) PLEASE CLEAN NEUTRAL CONDUCTORS AT TERMANAL BAR IN PANEL 5.) FLOOR PLUGS MISSING 6.) FILL UNUSED OPENING IN BOXES 7.) RESUPPORT THE CONDUITS THAT WHERE PULLED DOWN. 8.) PLEASE SUPPORT CONDUIT AS PER CODE. 9.) CORD CANNOT PASS THROUGH CEILING TILE ARE 400. CHECK ROOF AND SERVICE NEXT INSPECTION. |
| 01/08/2002 |
ELECTRIC - ABOVE CEILING |
|
Not ready for Inspection |
IVRS - Inspection 0000*LEFT PAPERWORK FOR TEMP C OF O & POWER FOR TEST. |