Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/30/2002 |
BUILDING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 04/29/2002 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) UNGROUNDED GFI 3 WIRE OUTLETS MUST BE GFCI PROTECTED AND UNGROUNDED LABEL OR REPLACE WITH 2 WIRE OUTLETS. SEE NEC 210-7 (D) (3) 2) CLOTHES CLOSETS CANNOT HAVE BARE BULB LIGHT FIXTURE SEE NEC 410-8 NOR OVER SHELF 3) NORTH BEDROOM ELECTRICAL OUTLET CANNOT BE ON KITCHEN GFCI CIRCUIT NEC 210-52 B-2 |