Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/05/2002 |
PLUMBING - ROUGH, SOIL |
|
Approved |
1.) SOIL WATER TEST IS OK 2.) P.O.C. OF NEW BLDG DRAIN TO EXSISTING BLDG. DRAIN IS OK 3.) OK FOR FLOORING. |
| 03/04/2002 |
PLUMBING - ROUGH, SOIL |
|
Denied |
IVRS - Inspection 0999*1.) 3" HORIZONTAL WASTE LINE REQUIRES 1/4" PER FT OF GRADE MIN. |
| 02/26/2002 |
PLUMBING - ROUGH, SOIL |
|
Denied |
IVRS - Inspection 0999*1.) MUST PROVIDE 10' HEAD WATER TEST ON SOIL. 2.) REMOVE FLOORING @ RESTROOM LOCATION FOR INSPECTION. 3.) ROUGH PLBG NOT TO PLAN. |