Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T01CM05730
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/11/2002 | BUILDING - FINAL | Approved | IVRS - Inspection 0000* | |
02/07/2002 | BUILDING - FINAL | Denied | IVRS - Inspection 0999*/ 1) FOR ITEM # 3090 PLUMBING FINAL; W.H. REMOVE FLEX LINE TO TPRV DISCHARGE LINE INSTALL RIGID COPPER. INSTALL PIPING WITH A 1/4" PER FT. MINIMUM SLOPE DOWNWARD FOR DRAINAGE. 2) FOR ITEM # 2090 ELECTRIC FINAL; ON WATER HEATER: WIRING MUST BE PROTECTED IN FLEX CONDUIT. AT BREAKER PANEL: IDENTIFY WATER HEATER WIRING WITH RED TAPE (WHITE WIRE) |