Permit: T01CM05725

Parcel: 12006196A


Addresses:

4075 S 6TH AV

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
02/14/2002 PLUMBING - FINAL Approved IVRS - Inspection 0000*1.) ALL CORRECTIONS MADE OK 2.) PLUMBING FINAL OK 3.) OK FOR C OF O PENDING ANY OTHER INSPECTIONS.
02/13/2002 PLUMBING - FINAL Denied IVRS - Inspection 0999*1.) H.C. WATER CLOSETS REQUIRE FLUSH HANDLE ON LARGE OPENING SIDE. 2.) WOOD SCREW SCREWED INTO ABS CLEAN OUT PLUGS IS NOT APPROVED USE TAPPED CLEAN OUT PLUG W/APPROVED SCREW.
01/17/2002 PLUMBING - FINAL Denied IVRS - Inspection 0999*1.) YOU HAVE WATER TESTED THE UNDERGROUND THATS ONE SECTION. NOW YOU NEED TO WATER TEST FROM SLAB THRU ROOF - SO THAT NO PIPE OR PITTING SHALL NOT HAVE BEEN SUBJECTED TO A WATER TEST. IN OTHER WORDS FILL THE ENTIRE SYSTEM UP WITH METER, TO THE HIGHET VENT ON THE ROOF.