Permit: T01CM05719

Parcel: 133033330

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
03/08/2002 FRAMING Approved IVRS - Inspection 0000*
03/07/2002 FRAMING Not ready for Inspection IVRS - Inspection 0000*/ 1) NEED 1' AIR GAP FO WATER SOFTNER LINE 2) HTT/22 REQUIRED 5/8 ANCHOR BOLT 3) WILL NEED ACCESS TO JACUZZI MOTOR 4) KEEP PEX WATER AWAY FROM CAN LIGHTS (MIN 12") 5) FIREPLACE CHANGE REQUIRED TO BE FIRE/BLKD, NOT DRAFT STOP, YOU HAVE WALLS THAT ARE OPEN TO CONCEALED AREAS RETHINK 6) FIREPLACE HEARTH SAFTEY STRIP TO GO 1/2 UNDER FIREPLACE 1/2 STICKING OUT SEE INSTALLATION BOOK 7) BLK AROUND FURNACE DUCTS CEILING GARAGE 8) FIRE BLOCK AT DRYER VENT CHASE TO ROOF AREA 9) NEED CROSS SECTION OF #2 SHEAR WALL (SHEAR TRANSFER) 10) CAN LIGHT IN NICHE AT HALLWAY FIREBLOCK CHASE