Inspection History Details
Inspection Status: Denied
Inspection History: BUILDING - FINAL
Permit Number - T01CM05712
Inspection Description - BUILDING - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/20/2002 | BUILDING - FINAL | Denied | IVRS - Inspection 0999*1.) TPRU DISCHARGE UNDERSIZED AND ROUTED TO ROOF. IT MUST BE 3./4" AND GO DOWN HILL TO OUTSIDE 2.) NO EXPOSED WOOD ALLOWED IN RETURN AIR PLENUM. 3.) BLANK OFF UNUSED OPENING IN SUBPANEL. 4.) I NEED FINAL INSPECTION REPORTS FROM ELECTRIC, PLUMBING & MECHANICAL INSPECTORS. | |
07/19/2002 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection 0000* |