Permit: T01CM05709

Parcel: 11516023B

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T01CM05709

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/08/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
07/01/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*FINISH ITEM #7 A #6 GROUND TO DIMMER PACKS.
06/28/2002 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*
03/06/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*OK TEMP C OF O 1.) PLEASE COMPLETE #5,6, & 7 AND RECALL.
02/15/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) TRAC LIGHTING TO HAVE SUPPORT WIRES 410-16. 2.) RECEPTACLES IN CEILING NEED SUPPORT WIRES 3.) STRAP MC CABLE AS PER CODE 334-10.4.) THE PLANS SPEC OUT 500 MCM COPPER WE HAVE 500 MEM ALUM. PLEASE VERIFY FROM ENGINEER IF THIS IS CORRECT OR INSTALL AS PLANS. 5.) PLANS ASK FOR 225A BREAKER, A 200 A IS INSTALLED PLEASE VERIFY 6.) INSTALLATION OF DINNER RACK FOR CONNECTION INSPECTION IS NEEDED. 7.) A #6. GROUND TO DIMMER PACK HAS NOT BEEN INSTALLED AT THIS TIME. 8.) PLEASE PROVIDE EXTENDER RINGS FOR RECEPTACLES INSTALLED IN CABINET. 110-27.