Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01CM05709
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/08/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
07/01/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*FINISH ITEM #7 A #6 GROUND TO DIMMER PACKS. | |
06/28/2002 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000* | |
03/06/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*OK TEMP C OF O 1.) PLEASE COMPLETE #5,6, & 7 AND RECALL. | |
02/15/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1.) TRAC LIGHTING TO HAVE SUPPORT WIRES 410-16. 2.) RECEPTACLES IN CEILING NEED SUPPORT WIRES 3.) STRAP MC CABLE AS PER CODE 334-10.4.) THE PLANS SPEC OUT 500 MCM COPPER WE HAVE 500 MEM ALUM. PLEASE VERIFY FROM ENGINEER IF THIS IS CORRECT OR INSTALL AS PLANS. 5.) PLANS ASK FOR 225A BREAKER, A 200 A IS INSTALLED PLEASE VERIFY 6.) INSTALLATION OF DINNER RACK FOR CONNECTION INSPECTION IS NEEDED. 7.) A #6. GROUND TO DIMMER PACK HAS NOT BEEN INSTALLED AT THIS TIME. 8.) PLEASE PROVIDE EXTENDER RINGS FOR RECEPTACLES INSTALLED IN CABINET. 110-27. |