Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T01CM05669
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/23/2002 | BUILDING - FINAL | Approved | IVRS - Inspection 0000* | |
08/22/2002 | BUILDING - FINAL | Denied | IVRS - Inspection 0999*/ 1) ABS PLASTIC VENTS ON ROOF MUST BE PROTECTED WITH LATEX PAINT 2) SIEMENS QP 50 AMP BREAKER NOT ALLOWED IN CUTLER-HAMMER ELECTRIC SERVICE PANEL 3) SOIL MUST BE 4" BELOW WEEP SCREED AND GRADED 2 PERCENT AWAY FROM HOUSE 5 FT 4) STOOP REQUIRED STOOP AT GUEST 5) SOFTENER DISCHARGE REQUIRES AND AIR GAP FITTING |