Permit: T01CM05669

Parcel: 123110920


Addresses:

1448 E LESTER ST


Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T01CM05669

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/23/2002 BUILDING - FINAL Approved IVRS - Inspection 0000*
08/22/2002 BUILDING - FINAL Denied IVRS - Inspection 0999*/ 1) ABS PLASTIC VENTS ON ROOF MUST BE PROTECTED WITH LATEX PAINT 2) SIEMENS QP 50 AMP BREAKER NOT ALLOWED IN CUTLER-HAMMER ELECTRIC SERVICE PANEL 3) SOIL MUST BE 4" BELOW WEEP SCREED AND GRADED 2 PERCENT AWAY FROM HOUSE 5 FT 4) STOOP REQUIRED STOOP AT GUEST 5) SOFTENER DISCHARGE REQUIRES AND AIR GAP FITTING