Permit: T01CM05646

Parcel: 128010090


Addresses:

215 S CRAYCROFT RD

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
06/14/2002 MECHANICAL - FINAL Approved IVRS - Inspection 0000*OK FOR C OF O. ALL CORRECTION HAVE BEEN MADE.
06/13/2002 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*1.) CONDENSING UNIT #5 OVERFUSED. 2.) AH #5 NEEDS SECONDARY DRAIN. 3.) EXHAUST FAN NEEDS GREASE COLLECTOR. 4.) EXTEND CONDENSATE VENTS ABOVE OUTLET ON UNITS 5.) PERMANENTLY LABEL CONDENSORS ON ROOF & LABEL AIR HANDLERS. RECALL FOR FINAL.