Permit: T01CM05646

Parcel: 128010090


Addresses:

215 S CRAYCROFT RD


Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T01CM05646

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
06/14/2002 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection 0000*
05/14/2002 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection 0999*NOTE: UNITS ABOVE & CEILINGS DO NOT HAVE SECONDARY DRAIN PANS. THIS IS A CODE REQUIREMENT OVERFLOW SENSORS WILL BE ACCEPTABLE. OK FOR PARTIAL CEILING TILES.
05/06/2002 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*OK FOR CEILING TILES LEAVE OUT UNDER UNITS. FIRE WRAP NEEDS PINS ON SECTIONS WHERE THERE ARE NO BANDS. DO NOT TAPE SLAMS NEED TO SEE MIN. 3" OVERLAP. PROVIDE SECONDARY DRAIN PANS UNDER AIR HANDLERS AS PER SECTION 307.2.3 2000 IMC.
04/16/2002 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*OK FOR SHEET ROCK.
03/21/2002 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*