Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date |
Description |
Inspector |
Results |
Comments |
| 03/22/2002 |
EXT METAL CLIPS/EXT SHEATHING |
|
Approved |
IVRS - Inspection 0000* |
| 03/18/2002 |
EXT METAL CLIPS/EXT SHEATHING |
|
Denied |
IVRS - Inspection 0999*/ 1) FIRE BLOCK DRYER VENT, VENT OUTSIDE OF WALL, NAIL PROTECT DRYER VENT 2) INADEQUATE SIDE CLEARANCE TO HALL W/C-15" REQUIRED-PRESENTLY 13 1/2 3) W/C FLOOR FLANGES NOT IN 4) LAUNDRY TRAP REQUIRES 2 PIPE DIAMETERS TO VENT 5) PROVIDE WHOLE HOUSE DWV WATER TEST PER UPC SECTION 712.2 6) LOW GAS PRESSURE TEST. MUST BE A MINIMUM OF 10 PSI 7) SUPPORT GAS LINE AT 10' ON CENTER 8) CLIP TJI'S AT INTERIOR BEARING WALL PER B/6 9) CLIP PORCH RAFTERS AND BEAMS PER F/6 AND G/6 10) PLUMBING PLAN CALLS FOR KITCHEN VENT TO ROOF. AAV USER. REVISE PLAN TO AS BUILT AND HAVE APPROVED BY CITY OF TUCSON 11) SUPPORT 1/2 GAS LINE AT 6' ON CENTER. 3/4" AT 8' ON CENTER PLUS 1" AND ABOVE AT 10' ON CENTER 12) GAS LINE NOT PER PLAN 3/4" REQUIRES TO FP AND OUTSIDE 13) MECHANICAL PLAN CALLS FOR RIGIN DUCT. FLEX USED REVISE PLAN TO ASBUILT AND HAVE APPROVED BY CITY OF TUCSON 14) PROVIDE WATER HEATER COMBUSTION RELIEF AIR 15) REVISE PLAN FOR USE OF NON SIMPSON HARDWARE-SEE V-13 16) STOPPED INSPECTION-TOO MANY ITEMS |
| 02/25/2002 |
EXT METAL CLIPS/EXT SHEATHING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) HOUSE ROOF OK TO DRY, PORCH NOT READY 2) LEDGER CLIPS OK SHEATHING AND HOLDOWNS NOT NAILED |