Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T01CM05628

Parcel: 10309074B


Addresses:

3875 N COMMERCE DR


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T01CM05628

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/22/2002 ELECTRIC - FINAL Approved VIEWED 180 OF UNDERGROUND CONDUIT FROM THE INSIDE WITH A CAMARA VIEW. 3 90'S WERE ENCOUNTERED. COUPLINGS AT THE BEGINNING OF RUN HAD LARGER GAPS AND LESS GLUE PRESENT THAN AT THE END OF THE RUN. CONDUIT COLOR IS CONSISTAN THROUHOUT RUN. CONDUITS IS COVERED BY CONCRETE ON OUTSIDE OF BUILDING THIS METHOD WAS APPROVED BY DAVE MANN. 1.) COMPLETE ITEMS 4,5,7, & 9 OF PREVIOUS INSPECTIONS.
08/15/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1.) PLEASE TIGHTEN CONDUIT FITTING AT BOX UNDER SALES COUNTER. 2.) PANEL A & B TO BE DISCONNECTED UNTILL COMPLIANCE IS MEET. FOLLOW UP WILL BE MADE TO ASSURE POWER IS DISCONNECTED NON COMPLIANCE WILL BE ACTION FOR ALL POWER DISCONNECTION. 3.) RECEPTICALS WITHIN 6' OF SINK OR BASIN TO BE GFCI AS PER PLAN NOTES. 4.) WHAT IS THE "CE" TYPE LIGHT TO BE. PLAN CALL FOR 8' STRIP OR 4' BATTERY PACK LIGHT. 5.) GROUND WIRE TO BE IN ALL RACEWAY AS PER PLAN NOTES. 6.) PLEASE LABEL DISCONNECTS 7.) WIRING CONDUCTORS TO BE COLOR CODED. AS PER 210-5 NEC & AMEDED CODES. 8.) TIGHTEN SEATITE FITTINGS 9.) MAINTENCE RECEPTACLES TO BE WITHIN 25' OF MECHANICAL UNITS.