Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date |
Description |
Inspector |
Results |
Comments |
| 07/24/2002 |
ELECTRIC - CABLE DROP |
|
Approved |
IVRS - Inspection 0000* |
| 07/17/2002 |
ELECTRIC - CABLE DROP |
|
Denied |
IVRS - Inspection 0999*BONDING DEVICES ARE NEEDED AT ALL METAL FITTING AT SERVICE PER CODE 250-94. 2.) PLEASE BOND GUTTER 250-96. 3.) CONDUCTOR FOR GROUNDING SMALLER THAN LUG LISTING 3/0 4.) LOOSE FITTING AT 2ND DISCONNECT 5.) PLEASE LABEL DISCONNECTS. |