Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
Permit Number - T01CM05628
Inspection Description - ELECTRIC - CABLE DROP
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/24/2002 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection 0000* | |
07/17/2002 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection 0999*BONDING DEVICES ARE NEEDED AT ALL METAL FITTING AT SERVICE PER CODE 250-94. 2.) PLEASE BOND GUTTER 250-96. 3.) CONDUCTOR FOR GROUNDING SMALLER THAN LUG LISTING 3/0 4.) LOOSE FITTING AT 2ND DISCONNECT 5.) PLEASE LABEL DISCONNECTS. |