Permit: T01CM05628

Parcel: 10309074B


Addresses:

3875 N COMMERCE DR

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
07/24/2002 ELECTRIC - CABLE DROP Approved IVRS - Inspection 0000*
07/17/2002 ELECTRIC - CABLE DROP Denied IVRS - Inspection 0999*BONDING DEVICES ARE NEEDED AT ALL METAL FITTING AT SERVICE PER CODE 250-94. 2.) PLEASE BOND GUTTER 250-96. 3.) CONDUCTOR FOR GROUNDING SMALLER THAN LUG LISTING 3/0 4.) LOOSE FITTING AT 2ND DISCONNECT 5.) PLEASE LABEL DISCONNECTS.