Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T01CM05628
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/10/2002 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection 0000*OFFICE STORAGE BREAKROOM OK 15' -21/2 PVC AT REAR NW CORNER SERVICE ENTRANCE TO DISCONNECT OK TO COVER HAS TO BE ENCASED IN CONCRETE. | |
07/01/2002 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0999*1.) INSTALL SUPPORTS FOR CONDUIT AS PER CODE. WITHIN 3' OF BOXES AND FITTINGS AND EVERY 10" THEREAFTER. 2.) TIGHTEN LOOSE SET SCREW FITTINGS. 3.) DATA TO BE SUPPORTED CORRECLTY. 4.) SUPPORT OF ELECTRICAL ABOVE CIELING TO BE INDEPENDANTLY SUPPORTED 300-11. 5.) WEN USING MANUFACTURES HOLD DOWN CLIPS THEY NEED TO BE EFFECTIVE. 6.) WHERE IS ELECTRIC FOR SIGN AS PER PLANS. |