Inspection Status: Denied
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/10/2001 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) RELIEF VENT REQUIRED AT WATER HEATER 2) PTR LINE SHALL EXTEND TO OUTSIDE ? 3) TRAP REQUIRED AT WASHING MACHINE DRAIN 4) GFI RECEP REQUIRED AT LAVATORY 5) COOLER FUZED BOX IN A HAZARDOUS CONDITION, NO EXPOSED WIRE ALLOWED THEY SHALL BE IN CONDUIT 6) NEED APPROVED DRAWINGS ON SITE 7) POSSIBLE PROBLEM WITH BEDROOM WINDOW |
| 11/26/2001 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) PROVIDE SMOKE DETECTORS AT BEDROOMS 2) POST ADDRESS ON STRUCTURE 3) POST ADDRESS ON ELECTRIC PANEL 4) LABEL CIRCUIT BREAKERS AT ELECTRIC PANEL 5) PRESSURE RELIEF AT WATER HEATER REQUIRES TO DRAIN TO EXTERIOR OF HOME 6) REMOVE TAPE AT DOUBLE WALL TO SINGLE WALL FLUE PIPE AT WATER HEATER 7) PROVIDE ELECTRIC OUTLETS AT WALLS REQUIRED PER CODE 8) PROVIDE COMBUSTION RELIEF VENTS AT LOCATION OF WATER HEATER 9) LAUNDRY DRAIN REQUIRED TO BE 2" MINIMUM PER CODE |
| 11/21/2001 |
BUILDING - FINAL |
|
Denied |
1) POST ADDRESS ON STRUCTURE 2) POST ADDRESS AT SERVICE PANEL 3) LABEL ALL SWITCHES AT PANEL 4) PROVIDE ANTI-SIPHON DEVICES AT ALL EXTERIOR HOSE BIBS |
| 11/16/2001 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) NO PLANS/PERMITS |