Inspection History Details
Inspection Status: Approved
Inspection History: REINFORCED MASONRY PRE-GROUT
Permit Number - T01CM05607
Inspection Description - REINFORCED MASONRY PRE-GROUT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/26/2002 | REINFORCED MASONRY PRE-GROUT | Approved | IVRS - Inspection 0000* | |
02/14/2002 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection 0000* | |
02/13/2002 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection 0000*TOW MAIN; 4' COLUMNS | |
02/11/2002 | REINFORCED MASONRY PRE-GROUT | Partial Approval | PARTIAL 16' | |
02/08/2002 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection 0000*16' | |
02/07/2002 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection 0000*PARTIAL -12' | |
02/06/2002 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection 0000*3L OK MAINTAIN 48 BAR DIAMETER LAP SPLICE, OR, 62 BAR DIAMETERS WHEN 2 BARS IN SAME CELL ARE LESS THAN 2" APART. | |
02/05/2002 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection 0000*KEEP GROUT DOWN 2'-4" FROM TOP OF 2ND LIFT. | |
02/01/2002 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection 0000*PARTIAL IL EXCEPT NEED 30% INCREASE IN LAP LENGTH WHERE 2 BARS ARE IN SAME CELL. | |
01/31/2002 | REINFORCED MASONRY PRE-GROUT | Not ready for Inspection | IVRS - Inspection 0000*NOT READY. |