Permit: T01CM05607

Parcel: 132191160


Addresses:

2175 E IRVINGTON RD


Inspection Status: Approved

Inspection History: REINFORCED MASONRY PRE-GROUT

Permit Number - T01CM05607

Inspection Description - REINFORCED MASONRY PRE-GROUT

Inspection Status - Approved

Date Description Inspector Results Comments
07/26/2002 REINFORCED MASONRY PRE-GROUT Approved IVRS - Inspection 0000*
02/14/2002 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000*
02/13/2002 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000*TOW MAIN; 4' COLUMNS
02/11/2002 REINFORCED MASONRY PRE-GROUT Partial Approval PARTIAL 16'
02/08/2002 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000*16'
02/07/2002 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000*PARTIAL -12'
02/06/2002 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000*3L OK MAINTAIN 48 BAR DIAMETER LAP SPLICE, OR, 62 BAR DIAMETERS WHEN 2 BARS IN SAME CELL ARE LESS THAN 2" APART.
02/05/2002 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000*KEEP GROUT DOWN 2'-4" FROM TOP OF 2ND LIFT.
02/01/2002 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000*PARTIAL IL EXCEPT NEED 30% INCREASE IN LAP LENGTH WHERE 2 BARS ARE IN SAME CELL.
01/31/2002 REINFORCED MASONRY PRE-GROUT Not ready for Inspection IVRS - Inspection 0000*NOT READY.