Permit: T01CM05605

Parcel: 11708211C


Addresses:

939 S 10TH AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/08/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*POWER SUBJECT TO LAST INSPECTOR .
11/04/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0920*PLEASE IDENTIFY THE MAIN SWITCHES. USE PERMANENT METALLIC EMBOSSED STRIPS. IDENTIFY THE CIRCUITS FEEDING THE A/C SWITCHES OUTSIDE. ARRANGE TO LEAVE DOOR UNLOCKED.
11/01/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*NEED POSITIVE ATTACHMENT OF LAY IN FIXTURE TO CEIL. GRID. SYSTEM. USE APPROVED CLIPS, SCREWS OR OTHER ACCEPTABLE MEANS. NEC 410-16 (C). PLEASE NEED A SUPPORT FOR 2" CONDUIT PANEL B REMOVE TEMP. RECEPTACLE AT NORTH END OF MODULAR RECEPTS ON TEMP POLE. NOTE: RECEIVED LETTER OF LICENSED ELECTRICAL CONTRACTORS OK.
10/04/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999$
10/03/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*LOCKED PLEASE RECALL INSPECTION.
10/02/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0920*
09/27/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0245*1.) PULL UP AND SUPPORT LIGHT FIXTURE WHIPS THAT ARE SAGGING ON TOP OF CEILING PANELS. 2.) CHECK ALL FIXTURE TO MAKE SURE THEIR IS 2 SIESMIC TIES DIAGONALLY ATTACHED AND A MINIMUM OF ONE SCREW EACH END THROUGH 'T' BAR AND INTO FIXTURE. 3.) UNLOCK SERVICE EQUIPMENT.
09/25/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0920*LOCKED HAVE ALL PLANS ALL APPROVALS RECALL INSPECTION.