Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/08/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*POWER SUBJECT TO LAST INSPECTOR . |
| 11/04/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0920*PLEASE IDENTIFY THE MAIN SWITCHES. USE PERMANENT METALLIC EMBOSSED STRIPS. IDENTIFY THE CIRCUITS FEEDING THE A/C SWITCHES OUTSIDE. ARRANGE TO LEAVE DOOR UNLOCKED. |
| 11/01/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*NEED POSITIVE ATTACHMENT OF LAY IN FIXTURE TO CEIL. GRID. SYSTEM. USE APPROVED CLIPS, SCREWS OR OTHER ACCEPTABLE MEANS. NEC 410-16 (C). PLEASE NEED A SUPPORT FOR 2" CONDUIT PANEL B REMOVE TEMP. RECEPTACLE AT NORTH END OF MODULAR RECEPTS ON TEMP POLE. NOTE: RECEIVED LETTER OF LICENSED ELECTRICAL CONTRACTORS OK. |
| 10/04/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999$ |
| 10/03/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*LOCKED PLEASE RECALL INSPECTION. |
| 10/02/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0920* |
| 09/27/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*1.) PULL UP AND SUPPORT LIGHT FIXTURE WHIPS THAT ARE SAGGING ON TOP OF CEILING PANELS. 2.) CHECK ALL FIXTURE TO MAKE SURE THEIR IS 2 SIESMIC TIES DIAGONALLY ATTACHED AND A MINIMUM OF ONE SCREW EACH END THROUGH 'T' BAR AND INTO FIXTURE. 3.) UNLOCK SERVICE EQUIPMENT. |
| 09/25/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0920*LOCKED HAVE ALL PLANS ALL APPROVALS RECALL INSPECTION. |