Permit: T01CM05605

Parcel: 11708211C


Addresses:

939 S 10TH AV

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
06/13/2002 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*OK TO CLEAR CABLE DROP TRENCH & METER CAN SUBJECT TO TEP APPROVAL. PLEASE CALL TEP FOR FIELD TECH INSPECTION OF SITE.
05/24/2002 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0920*LOCKED PLEASE RECALL NEED NAME OF LICENSED ELECTRICAL CONTRACTOR
04/19/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*NOTES OK SOUTH KITCHEN WALL ONLY. 1.) ROMEX TERMINATION IN LOADCENTER IN HALLWAYS NEED TO BE CLAMPED INDIVIDUALLY WITH LISTED CONNECTORS 110-3NEC. 2.) BACK TO BACK BOXES IN FIRE WALLS NOT ALLOWED IN SAME STUD CAVITY, UNLESS FIRE TAPED WITH LISTED FRIE PUTTY. 3.) ROMEX WIRING BUNDLED TOGETHER FOR LENGTHS GREATER THAN 2' NEED TO BE DE-RATED.