Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 08/13/2002 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 08/12/2002 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) RISER OPENINGS CANNOT EXCEED 4" 2) NO OPENING ALLOWED IN GUARD RAILING LARGER THAN 4" 3) CLEANOUT MUST HAVE THREADED CAP TRIM GRADE 4) LABEL ALL CIRCUITS IN SERVICE PANEL 5) PROTECT/BURY GROUND/BOND WIRES 6) SHEET METAL SELF TAPPING SCREWS NOT ALLOWED TO SECURE SERVICE PANEL DEAD FRONT 7) WATER HEATER T&P LINE MUST EXHAUST DOWN 8) CLOTHES DRYER MUST HAVE A 4 PRONG PLUG AND OUTLET 9) DRYER OUTLET MISSING COVER |
| 04/17/2002 |
FRAMING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) ITEMS ONE AND TWO FROM 4/15/02 NOT COMPLIED WITH 2) BOND WATER AT WATER HEATER NOT TO T & P LINE IN EXPOSED AREA 3) OK TO INSULATE AND DRYWALL |
| 04/15/2002 |