Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T01CM05590
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/06/2002 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000* 1.) PLBG. FINAL IS OK 2.) OK FOR C OF O. | |
04/29/2002 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*1.) H.C. LAVATORY IN RM K A4 MUST BE NO LOWER THAN 29" FROM F.F. TO BOTTOM OF LAV NO HIGHER THAT 34" TO TOP OF LAV (ADA SPECS) 2.) MUST CAULK H.C. LAV & WATER CLOSET 3.) H.C. WATER CLOSET HANDLE MUST BE ON OPEN SIDE OF RM (ADA SPECS.) 4.) WATER P & T DRAIN CAN HAVE NO FLEX LINES 5. WATER HTR REQUIRES EXPANSION TANK 6.) DISHWASHER DISCHARGE HOSE MUST BE ANCHORED AS HIGH AS POSSIBLE TO BOTTOM OF COUNTER TOP 7.) PUBLIC RESTROOMS WATER CLOSET SEATS MUST BE OPEN FRONT LESS LID. |