Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 01/22/2002 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 01/10/2002 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*OK WALLS NORTH HALF OF BLD. |
| 12/27/2001 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0245*NOTES 1. J-BOXES IN HARD LIDS MUST BE ACCESSABLE 2.) CONDUITS MUST BE SUPPORTED WITHIN 3' EACH J-BOX. 3.) FLEX TO BE SUPPORTED WITHIN 12" AND AT 4 1/2" INTERVALS. EXCEPTION 6' OR LESS. 3.) GROUND PIGTAILS REQUIRED IN DEVICE BOXES.4.) SEE WRITE UP LAST INSPECTION 5.) LOOSE FITTINGS. |
| 12/26/2001 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0245*1.) SUPPORT EMT & FLEX PER N.E.C. ART 348 ART 350. 2.) USE BOX OFFSET OR PROPER BENDS ON CONDUIT AND SUPPORT PER ABOVE DO NOT FORCE CONDUIT TO STUDS TO SUPPORT, 110-12NEC. 3.) INSTALL GROUND TAILS IN ALL METAL BOXES FOR GROUNDING OF DEVICES, 250-148 NEC. 4.)INSTALL GROUND IN ALL CONDUITS AS PER PLAN SPECS. 5.) NEED VERIFICATION OF L-11 LICENSED CONTRACTOR,NAME & PH#. |