Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T01CM05590

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
01/22/2002 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
01/10/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK WALLS NORTH HALF OF BLD.
12/27/2001 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0245*NOTES 1. J-BOXES IN HARD LIDS MUST BE ACCESSABLE 2.) CONDUITS MUST BE SUPPORTED WITHIN 3' EACH J-BOX. 3.) FLEX TO BE SUPPORTED WITHIN 12" AND AT 4 1/2" INTERVALS. EXCEPTION 6' OR LESS. 3.) GROUND PIGTAILS REQUIRED IN DEVICE BOXES.4.) SEE WRITE UP LAST INSPECTION 5.) LOOSE FITTINGS.
12/26/2001 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0245*1.) SUPPORT EMT & FLEX PER N.E.C. ART 348 ART 350. 2.) USE BOX OFFSET OR PROPER BENDS ON CONDUIT AND SUPPORT PER ABOVE DO NOT FORCE CONDUIT TO STUDS TO SUPPORT, 110-12NEC. 3.) INSTALL GROUND TAILS IN ALL METAL BOXES FOR GROUNDING OF DEVICES, 250-148 NEC. 4.)INSTALL GROUND IN ALL CONDUITS AS PER PLAN SPECS. 5.) NEED VERIFICATION OF L-11 LICENSED CONTRACTOR,NAME & PH#.