Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/31/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*OK FINAL | |
| 01/29/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1.) NEED OFFICE FURNITURE CONNECTIONS. | |
| 01/06/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* 1.) FINISH INSTALLATION OF ELECTRIC AT RECEPTION AREA 2. AN APPROVED EXTENDER RING WILL BE NEEDED WHERE MORE THAN 1/4" FROM BOX TO DEVICE. 3.) WATER HEATER NEED VERIFICATION OF CORD CONNECTION IF NOT A DISCONNECTING MEANS IS NEEDED 4.) PLEASE SEAL HOLE IN RATED CORRIDOR, WE ALSO HAVE MORE THAN 100 SQ IN FATED WALL. 5.) PLEASE VERIFY FUSES, PLANS CALL FOR JJ WE HAVE RK5 INSTALLED 6.) PLEASE PROVIDE CITY APPROVED LETTER FOR PARKING LOT LIGHTS. 7.) OK POLE HEAD MAKE UP FINISH POLE SUBJECT TO APPROVAL #6. |
|
| 12/23/2002 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000* |