Permit: T01CM05579

Parcel: 123051640

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
04/15/2002 FRAMING Approved IVRS - Inspection 0000*
04/05/2002 FRAMING Not ready for Inspection IVRS - Inspection 0000*/ 1) LEFT PIPE DEAGRAM ON SITE FOR GAS LINE THATS UNDER SIZED, PLEASE DON'T LOOSEN IT, STARTS WITH 1 14/' ALL THE WAAY TO NEW FURNACE ROOM 1" TO DRYER, 3/4 TO RANGE, FIREPLACE PATCH WALL AT BACK SIDE OF FIRE BOX, MOVE COMBUSTIBLES 2" AWAY
04/02/2002 FRAMING Not ready for Inspection IVRS - Inspection 0000*/ 1) NEED AS BUILT PIPE DIAGRAM FOR GAS LINE 1" PIPE IN FROM METER. PLAN DOES NOT SHOW ALL APPLIANCES 2) ISOLATE GAS LINE FROM RETURN PLENIUM, EAST FURNACE /W/HEATER CANNOT RUN T.P.R. LINE UP THRU ROOF 3) COMB/RELIEF WEST FURNACE ROOM MUST GET AIR FROM VENTED ATTIC SPACE 4) 2" CLR. AT OLD FIREPLACE TO COMBUSTIBLES 5) NEED TEP/GLASS WINDOW AT GARAGE MAN DOOR 6) INSTALL CONDENSATION LINES BOTH UNITS