Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/28/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 05/22/2002 |
ELECTRIC - FINAL |
|
Denied |
CHECK FOR ALL LISTING 1.) LOOSE CONNECTION 2.) MAIN BOND JUMPER 3.) LUG RATED FOR 3/0 TO 800 MCM ALSO NEED TO KNOW SIZE OF MAIN BOND JUMP. 3.) CARPET MACHINE REQUIRE 30 AMPS. ON VACUME NEED RACEWAY UP TO TERMINATION AREA. WHAT SIZE IS PANEL FEEDERS ? UL. LISTING FOR LIGHTS SUITABLE FOR DAMP LOCATION. NOT ENTERED |