Permit: T01CM05575

Parcel: 13715144B


Addresses:

5627 S MISSION RD

Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Date Description Inspector Results Comments
05/30/2002 ELECTRIC - UNDERGROUND Approved
04/29/2002 ELECTRIC - UNDERGROUND Partial Approval 5-3/4" PVC'S FROM MECH ROOM TO VAC ISLANDS CONTRACTOR TO POUR CONCRETE OVER CONDUITS NOT 24" DEEP BY SIDE WALKS.
04/26/2002 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*MECHANICAL EQUPMENT ROOM CONDUIT UNDERGROUND APPROVED SECONDARY CONDUIT APPROVED.
04/15/2002 ELECTRIC - UNDERGROUND Denied IVRS - Inspection 0920*
04/15/2002 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*2" PVC FEEDER TO INTERIOR SUB PANEL. 6 -3/4" PVC CONDUITS STUB OUT OF DOOR WAY @ EQUIP ROOM.COVERED 2" TO SUB PANEL. MUST UNCOVER ALL RECALL INSPECTION.
04/03/2002 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*DRY BUILDING UNDERGROUND.
03/28/2002 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*PARTIAL FOR SECONDARY CONDUIT TO W/IN 10FT OF UTILITY TRANSFORMER.