Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/12/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 08/09/2002 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 08/02/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* NEED TO RECTIFY CLEARANCE PROBLEM IN FRONT FO MC. NEED PROPER O.C. PROTECTION FOR SECONDARY OF 35KVA TRANSFORMER. |
| 07/19/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*1.) INSTALLED PLYWOOD IN FRONT OF METAL FROMING FOR POOL HEATER. A CLEARANCE OF 38" HAS BEEN ACCOMPLISHED. WILL NEED TO CONSULT W/OFFICE PRIOR TO ANY DECISION. 2.) PLEASE USE PERMANENT I.D. TAGS FOR EQUIP. EG. @MCC "30 KVA/PHP" 3.) BOND TRANSFORMER 30 KVA PER NEED BUILD STEEL FOR TRANS. BOND.4.) A DISCONNECT REQUIRED FOR PROPER O.C. PROTECTION W/IN 10 FT. OF |
| 06/24/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999* |