Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 02/12/2002 |
ELECTRIC - FINAL |
|
Approved |
|
| 02/08/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) RECEPTACLE BY KIT COUNTER CALLS TO BE GFI. 2.) THE NEW GROUNDING SYSTEM (2 RODS & GAS BOND) HAVE TO TIE INTO THE NEUTRAL AT THE SERVICE ONE TIME CANNOT LOCATE THE WATER BOND TO SERVICE. 3.) THE NEW 500 MCM CONDUCTORS THAT TIE INTO THE MAIN ENCLOSURE ARE COPPER THEY ARE LANDED ON A LUG RATED FOR COPPER OR ALUM HOWEVER ALUMINIM & COPPER CANNOT GO TOGETHER IN THE SAME LUG. 6.) MARK ALL PANELS A-B-C. OK TO CLEAR 1615 E FT LOWELL AAP2. |