Permit: T01CM05558

Parcel: 113061280

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/12/2002 ELECTRIC - FINAL Approved
02/08/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1.) RECEPTACLE BY KIT COUNTER CALLS TO BE GFI. 2.) THE NEW GROUNDING SYSTEM (2 RODS & GAS BOND) HAVE TO TIE INTO THE NEUTRAL AT THE SERVICE ONE TIME CANNOT LOCATE THE WATER BOND TO SERVICE. 3.) THE NEW 500 MCM CONDUCTORS THAT TIE INTO THE MAIN ENCLOSURE ARE COPPER THEY ARE LANDED ON A LUG RATED FOR COPPER OR ALUM HOWEVER ALUMINIM & COPPER CANNOT GO TOGETHER IN THE SAME LUG. 6.) MARK ALL PANELS A-B-C. OK TO CLEAR 1615 E FT LOWELL AAP2.