Permit: T01CM05557

Parcel: 13416205D


Addresses:

7201 E 22ND ST


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T01CM05557

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
01/08/2002 PLUMBING - INTERMEDIATE Approved IVRS - Inspection 0000*
01/07/2002 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0000*REMOVE TOILET TO COMPLETE INTERMEDIATE INSPECTION.
01/04/2002 PLUMBING - INTERMEDIATE Denied
01/03/2002 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection 0000*1.) NEED TO SEE CLOSET FLANGES BEFORE FINAL INSPECTION.
12/28/2001 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*1.) FINISH STRAPPING COPPER 2.) WATER LINE MAY NOT RUN ABOVE ELECTRIC SERVICE PANEL. 3.) ABS WATER TEST OK TRAP ARM OK.
12/21/2001 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*1. NO CORRECTIONS MADE SINCE LAST INSPECTION. 2. BE SURE & HAVE WORK READY FOR INSPECTION OR RISK BEING ASSESSED A RE-INSPECTION FEE.
12/18/2001 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*1.) THE POINT OF VENT MAY NOT BE BELOW THE WEIR OF THE TRAP. 2.) STRAP AND BRACE ALL LOOSE COPPER.
12/12/2001 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*1.) WET VENTING IS LIMITED TO VERTICAL DRAINAGE PIPING RECEVING THE DISCHARGE FROM TRAP ARMS OF ONE AND TWO FIXTURE UNIT FIXTURES. 2.) WATER TEST INTERMEDIATE ABS DWV 3.) COPPER OK ISOLATE COPPER WHERE TOUCHING OTHER METALS.