Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T01CM05557
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/08/2002 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
01/07/2002 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0000*REMOVE TOILET TO COMPLETE INTERMEDIATE INSPECTION. | |
01/04/2002 | PLUMBING - INTERMEDIATE | Denied | ||
01/03/2002 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*1.) NEED TO SEE CLOSET FLANGES BEFORE FINAL INSPECTION. | |
12/28/2001 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999*1.) FINISH STRAPPING COPPER 2.) WATER LINE MAY NOT RUN ABOVE ELECTRIC SERVICE PANEL. 3.) ABS WATER TEST OK TRAP ARM OK. | |
12/21/2001 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999*1. NO CORRECTIONS MADE SINCE LAST INSPECTION. 2. BE SURE & HAVE WORK READY FOR INSPECTION OR RISK BEING ASSESSED A RE-INSPECTION FEE. | |
12/18/2001 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999*1.) THE POINT OF VENT MAY NOT BE BELOW THE WEIR OF THE TRAP. 2.) STRAP AND BRACE ALL LOOSE COPPER. | |
12/12/2001 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999*1.) WET VENTING IS LIMITED TO VERTICAL DRAINAGE PIPING RECEVING THE DISCHARGE FROM TRAP ARMS OF ONE AND TWO FIXTURE UNIT FIXTURES. 2.) WATER TEST INTERMEDIATE ABS DWV 3.) COPPER OK ISOLATE COPPER WHERE TOUCHING OTHER METALS. |