Permit: T01CM05510

Parcel: 140420200

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
11/26/2001 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection 0000*1.) ABS DWV UNDERGROUND OK WATER TEST TO TEN FEET OK 2.) OK TO BACKFILL 3.) WILL CHECK BACK PITCHED REVENT ON INTERMEDIATE 4.) PLUMBER: REMEBER, A DOUBLE SANTEE MAY BE USED WHEN THE BARREL OF THE FITTING IS AT LEAST 2 TWO PIPE SIZES LARGER THAN THE LARGEST INLET. USE A ABLE COMBO. OR A FIG. 5-.
11/20/2001 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection 0000*
11/20/2001 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection 0999*1.) WATER CLOSETS NOT INSTALLED PER PLAN. 2.) PLAN CALLS FOR 4" OVER SIZED VENT OK IF YOU WANT. 3.) WATER TEST REQ'D TO MINIMUM TEN FEET HEAD.