Permit: T01CM05502

Parcel: 115151540


Addresses:

624 W RILLITO ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/15/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
11/10/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
1.) FINISH RE HANGING LIGHTS
2.) WE STILL HAVE DATA LAYING ON GRID.
3.) SUPPORT EXHAUST FANS CLOSER TO FAN.
10/21/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0245*1.) CONDENSOR FUSES MUST BE HACR RATED. 2.) WTR. HTR. A/C AIR HANDLER, AND A/C CONDENSOR DISCONNECTS NEED PANEL & CIRCUIT I.D. 3.) NEED ENGINEERS WRITTEN APPROVAL FOR USE OF MC CABLE. PLAN SPEC'S. DO NOT MENTION USE OF MC. ONLY CONDUIT. THE FOLLOWING DISCREPANCIES EXIST BETWEEN PALN E1 AND THE INSTALLED SYSTEM. 1.) PANEL "A" REQUIRED A 200A MAIN C/B. 2.) THE ELECTRICAL SERVICE WAS TO BE AN SES WITH SUB-DISCONNECTS FOR PANEL A AND FUTURE PANEL "X"? 3.) THE ENGINEER OF RECORD MUST SUBMIT REVISED PLAN IS FOR REVIEW AND APPROVAL BY CITY PLANS REVIEWER 4.) THE REVISED PLAN MUST REFLECT THE "AS BUILT" CONDITION. CORRECTION NEEDED 1.) SECURE 2 X 4 DROP INS BY CLIPPING OR SCREWING BOTH ENDS TO F-GRID 2.) IDENTIFY EACH DISCONNECT SWITCH WITH THE POWER SOURCE. MAGIC MARKER BE USED INDOORS AND EMBOSSED METAL LABEL OUTDOORS.