Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/15/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 11/10/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* 1.) FINISH RE HANGING LIGHTS 2.) WE STILL HAVE DATA LAYING ON GRID. 3.) SUPPORT EXHAUST FANS CLOSER TO FAN. |
|
| 10/21/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*1.) CONDENSOR FUSES MUST BE HACR RATED. 2.) WTR. HTR. A/C AIR HANDLER, AND A/C CONDENSOR DISCONNECTS NEED PANEL & CIRCUIT I.D. 3.) NEED ENGINEERS WRITTEN APPROVAL FOR USE OF MC CABLE. PLAN SPEC'S. DO NOT MENTION USE OF MC. ONLY CONDUIT. THE FOLLOWING DISCREPANCIES EXIST BETWEEN PALN E1 AND THE INSTALLED SYSTEM. 1.) PANEL "A" REQUIRED A 200A MAIN C/B. 2.) THE ELECTRICAL SERVICE WAS TO BE AN SES WITH SUB-DISCONNECTS FOR PANEL A AND FUTURE PANEL "X"? 3.) THE ENGINEER OF RECORD MUST SUBMIT REVISED PLAN IS FOR REVIEW AND APPROVAL BY CITY PLANS REVIEWER 4.) THE REVISED PLAN MUST REFLECT THE "AS BUILT" CONDITION. CORRECTION NEEDED 1.) SECURE 2 X 4 DROP INS BY CLIPPING OR SCREWING BOTH ENDS TO F-GRID 2.) IDENTIFY EACH DISCONNECT SWITCH WITH THE POWER SOURCE. MAGIC MARKER BE USED INDOORS AND EMBOSSED METAL LABEL OUTDOORS. |