Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T01CM05498
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/24/2002 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection 0000* | |
| 06/17/2002 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection 0999*1.) PATCH DRYWALL BEHIND LIGHT FIXTURE ON FIRE WALLS. 2.) INSTALL RECEPTICALES & PLATES IN MEDIA CENTER CORRECTLY 3. MAINTAIN 1/8" CLEARENCE AROUND BOXES IN FIREWALL AS PER MANUFACTURE USE A FIRESTOP METHOD NOT DRYWALL MUD. 4.) PANEL IS IN VIOLATION OF WORKING CLEARENCE AS DISCUSSED FOR THIS PROJECT UNIT #1622 (45") CK ROOF NEXT TIME. | |
| 06/05/2002 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000*OK 1" CONDUIT FOR LIGHTING. OK TEMP PANEL 1 TIME ONLY WITHOUT MAIN DISCONNECTING MEANS. PER CODE 225-31,225-32,384-16,240 ALSO SPLIGES NOT ACCESSABLE AND BURIED. | |
| 04/25/2002 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000*OK 3/0 XHHW FOR TEMP POWER. | |
| 02/21/2002 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000* | |
| 01/16/2002 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000*OK 2-#4 UFER. OK 1-1" PVC UNDERSLAB. |