Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 03/12/2002 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* OK ROUGH ELECTRIC. |
| 03/11/2002 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*1. FINISH VDV CABLES. 2. FINISH WIRING DATA ROOM ELECTRIC OK |
| 03/03/2002 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*1.) HORZONAL DISTANCE SEPERATON IS REQUIRED TO BE 3" PER MANUFACTURES SPECIFICATION TO MAINTAIN FIRE RESISTANCE 110-3. 2.) ALL VDV CABLES TO BE INSTALLED 300. 3.) CABLE CLAMPS FOR MULTIGANG BOXES TO BE INSTALLED 373-5. 4.) FINISH CONTRUCTION OF DATA ROOM 5.) TIGHTEN BOX CLAMPS IN FAN BOXES. 6.) PROTECT CABLES ACROSS BOTTOM OF BEAM. OK PER ROCK. |