Permit: T01CM05495

Parcel: 11611001L


Addresses:

2525 W ANKLAM RD 08


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T01CM05495

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
03/12/2002 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000* OK ROUGH ELECTRIC.
03/11/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*1. FINISH VDV CABLES. 2. FINISH WIRING DATA ROOM ELECTRIC OK
03/03/2002 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*1.) HORZONAL DISTANCE SEPERATON IS REQUIRED TO BE 3" PER MANUFACTURES SPECIFICATION TO MAINTAIN FIRE RESISTANCE 110-3. 2.) ALL VDV CABLES TO BE INSTALLED 300. 3.) CABLE CLAMPS FOR MULTIGANG BOXES TO BE INSTALLED 373-5. 4.) FINISH CONTRUCTION OF DATA ROOM 5.) TIGHTEN BOX CLAMPS IN FAN BOXES. 6.) PROTECT CABLES ACROSS BOTTOM OF BEAM. OK PER ROCK.